PTS-200(F) Combination 2 In 1 Dc Test Set Insulation Resistance (Megohmmeter) And Dielectric Strength (Hipot) 0 – 200 kV @ 5 mA

The High Voltage, Inc. PTS-200(F) 0 – 200kVdc @ 5mA high voltage test set comes with Internal discharge/bleed down resistors. For ease of use all two-piece design DC Hipots come with a cable storage bin on the HV tank section.

PTS-200(F) Combination 2 In 1 Dc Test Set Insulation Resistance (Megohmmeter) And Dielectric Strength (Hipot) 0 – 200 kV @ 5 mA

Description

The HVI Combination 2 in 1 DC Tester Series are high voltage DC proof testers and HV Megohmmeters. Testing for dielectric strength and insulation resistance is now served with one instrument, saving money, size and weight. The PTS series is designed and constructed with field use in mind. It is rugged, reliable and contains the features needed for electrical maintenance testing of new or installed electrical apparatus.

 

  • Two range voltmeter and five range current meter
  • MΩ readings at any output voltage (w/ analogue meters)
  • Insulated return guard circuit to bypass stray leakage currents
  • Rugged case (field) with cushion grip handles and storage for leads
  • Internal discharge resistors to assist external bleed resistors
  • External safety interlock provision
  • Automatic transit protected meters rated 100 uA for durability
  • Benchtop or field controller available, analogue or digital metering

 

Input: 120V, 60Hz, 15A or 230V, 50/60Hz, 8A
Output: 0 – 200kVdc, 5mA, negative polarity, positive ground
Duty: Continuous

 

Voltmeter: 3.5″, scaled 0-80/200kVdc, ±2% FS accuracy
Currentmeter: 3.5″, scaled 0-1.0µAdc, ±2% FS with multipliers x1, x10, x100, x1k, x10k
Guard/ground load return: Yes
Megohmmeter: Scaled 100 -1MΩ with multipliers of x0.1, x1, x10, x100, x1k

 

Controls
Voltage output: Continuously adjustable up to max. voltage
Safety
Interlocks: Zero start and external interface
Protection: Surge and transient

 

Cable Length
Output cable: 6m EPR x-ray with alligator clamp
Ground lead: 6m with alligator clamp
Return lead: 6m with alligator clamp
Input line cord: 3m
Ground stick: 6m lead and clamp included
Size & Weight
Controls: 356mm w x 279mm d x 356mm h, 15kg
HV Tank: 330mm w x 368mm d x 775mm h, 68kg

Additional information

Input

120V, 60Hz, 15A or 230V, 50/60Hz, 8A

Output

0 – 200kVdc, 5mA, negative polarity, positive ground

Duty

Continuous

Metering - Voltage measurement

3.5″, scaled 0-80/200kVdc, ±2% FS accuracy

Metering - Currentmeter

3.5″, scaled 0-1.0µAdc, ±2% FS with multipliers x1, x10, x100, x1k, x10k

Metering - Guard/ground load return

Yes

Metering - Megohmmeter

Scaled 100 -1MΩ with multipliers of x0.1, x1, x10, x100, x1k

Controls - Voltage output

Continuously adjustable up to max. voltage

Safety - Interlocks

Zero start and external interface

Safety - Protection

Surge and transient

Cable Length - Output cable

6m EPR x-ray with alligator clamp

Cable Length - Ground lead

6m with alligator clamp

Cable Lengths - Return lead

6m with alligator clamp

Cable Length - Input line cord

3m

Cable Length - Ground stick

6m lead and clamp included

Size & Weight - Controls

356mm w x 279mm d x 356mm h, 15Kg

Size & Weight - HV Tank

330mm w x 368mm d x 775mm h, 68Kg

Product Enquiry