PTS-37.5(F) Combination 2 In 1 Dc Test Set Insulation Resistance (Megohmmeter) And Dielectric Strength (Hipot) 37.5 kV @ 10 mA

The HVI Combination 2 in 1 DC Tester Series are high voltage DC proof testers and HV Megohmmeters. Testing for dielectric strength and insulation resistance is now served with one instrument, saving money, size and weight. The PTS series is designed and constructed with field use in mind. It is rugged, reliable and contains the features needed for electrical maintenance testing of new or installed electrical apparatus.

PTS-37.5(F) Combination 2 In 1 Dc Test Set Insulation Resistance (Megohmmeter) And Dielectric Strength (Hipot) 37.5 kV @ 10 mA

Description

  • Continuously adjustable output voltage
  • Fixed overload, factory set to 120% of rated output current
  • Zero start and external interlock provision
  • Dual-range voltmeter
  • Five-range current meter 0-1.0 μA DC with x1, x10, x100, x1k, and x10k multipliers
  • Five-range megohmmeter 100-1 MΩ with x0.1, x1, x10, x100, and x1k multipliers
  • Ferro-resonant line regulator for output voltage stabilization
  • Guard/ground return circuit
  • Automatic transit protected meters
  • Rugged case with cushion grips
  • Transit protected meters

* Due to the ferro-resonant designed input voltage regulator, if an inverter is used for the voltage source it must produce a “true sine wave” output and not a “modified sine wave” (square wave). This model is input frequency sensitive: either 50Hz or 60Hz but not both. Please Specify when ordering.

 

Input 120V, 60Hz, 5A or 230V, 50/60Hz, 3A (±1% input voltage regulator)*
Output 0-37.5kVdc, 10mA, Negative polarity. positive ground.
Duty Continuous

 

Kilovoltmeter 3.5″, scaled 0-15/37.5kVdc, ±2% FS accuracy
Currentmeter 3.5″, scaled 0-1.0µAdc, ±2% FS with multipliers x1, x10, x100, x1k, x10k
Guard/ground load return Yes
Megohmmeter Scaled 100 -1MOhms with multipliers of x0.1, x1, x10, x100, x1k

 

Controls
Voltage output: Continuously adjustable up to max. voltage
Safety
Interlocks: Zero start and external interface
Protection: Surge and transient

 

Cable Length
Output cable: 6m shielded with alligator clamp
Ground lead: 6m with alligator clamp
Return lead 6m with alligator clamp
Input line cord 3m
Ground stick 6m lead and clamp included
Size & Weight
Controls: 356mm w x 279mm d x 356mm h, 23kg
HV Tank: Included in controls case

Additional information

Input

120V, 60Hz, 5A or 230V, 50/60Hz, 3A (±1% input voltage regulator)*

Output

0-37.5kVdc, 10mA, Negative polarity. positive ground.

Duty

Continuous

Metering - Kilovoltmeter

3.5″, scaled 0-15/37.5kVdc, ±2% FS accuracy

Metering - Currentmeter

3.5″, scaled 0-1.0µAdc, ±2% FS with multipliers x1, x10, x100, x1k, x10k

Metering - Guard/ground load return

Yes

Metering - Megohmmeter

Scaled 100 -1MΩ with multipliers of x0.1, x1, x10, x100, x1k

Controls - Voltage output

Continuously adjustable up to max. voltage

Safety - Interlocks

Zero start and external interface

Safety - Protection

Surge and transient

Cable Length - Output cable

6m shielded with alligator clamp

Cable Length - Ground lead

6m with alligator clamp

Cable Lengths - Return lead

6m with alligator clamp

Cable Length - Input line cord

3m

Cable Length - Ground stick

6m lead and clamp included

Size & Weight - Controls

356mm w x 279mm d x 356mm h, 23Kg

Size & Weight - HV Tank

Included in controls case