Description
- Continuously adjustable output voltage
- Fixed overload, factory set to 120% of rated output current
- Zero start and external interlock provision
- Dual-range voltmeter
- Five-range current meter 0-1.0 μA DC with x1, x10, x100, x1k, and x10k multipliers
- Five-range megohmmeter 100-1 MΩ with x0.1, x1, x10, x100, and x1k multipliers
- Ferro-resonant line regulator for output voltage stabilization
- Guard/ground return circuit
- Automatic transit protected meters
- Rugged case with cushion grips
- Transit protected meters
* Due to the ferro-resonant designed input voltage regulator, if an inverter is used for the voltage source it must produce a “true sine wave” output and not a “modified sine wave” (square wave). This model is input frequency sensitive: either 50Hz or 60Hz but not both. Please Specify when ordering.
Input | 120V, 60Hz, 5A or 230V, 50/60Hz, 3A (±1% input voltage regulator)* |
Output | 0-37.5kVdc, 10mA, Negative polarity. positive ground. |
Duty | Continuous |
Kilovoltmeter | 3.5″, scaled 0-15/37.5kVdc, ±2% FS accuracy |
Currentmeter | 3.5″, scaled 0-1.0µAdc, ±2% FS with multipliers x1, x10, x100, x1k, x10k |
Guard/ground load return | Yes |
Megohmmeter | Scaled 100 -1MOhms with multipliers of x0.1, x1, x10, x100, x1k |
Controls | |
---|---|
Voltage output: | Continuously adjustable up to max. voltage |
Safety | |
Interlocks: | Zero start and external interface |
Protection: | Surge and transient |
Cable Length | |
---|---|
Output cable: | 6m shielded with alligator clamp |
Ground lead: | 6m with alligator clamp |
Return lead | 6m with alligator clamp |
Input line cord | 3m |
Ground stick | 6m lead and clamp included |
Size & Weight | |
Controls: | 356mm w x 279mm d x 356mm h, 23kg |
HV Tank: | Included in controls case |