Description
The HVI Combination 2 in 1 DC Tester Series are high voltage DC proof testers and HV Megohmmeters. Testing for dielectric strength and insulation resistance is now served with one instrument, saving money, size and weight. The PTS series is designed and constructed with field use in mind. It is rugged, reliable and contains the features needed for electrical maintenance testing of new or installed electrical apparatus.
- Two range voltmeter and five range current meter
- MΩ readings at any output voltage (w/ analogue meters)
- Insulated return guard circuit to bypass stray leakage currents
- Rugged case (field) with cushion grip handles and storage for leads
- Internal discharge resistors to assist external bleed resistors
- External safety interlock provision
- Automatic transit protected meters rated 100 uA for durability
- Benchtop or field controller available, analogue or digital metering
Input: | 120V, 60Hz, 15A or 230V, 50/60Hz, 8A |
Output: | 0 – 300kVdc, 5mA, negative polarity, positive ground |
Duty: | Continuous |
Voltmeter: | 3.5″, scaled 0-120/300kVdc, ±2% FS accuracy |
Currentmeter: | 3.5″, scaled 0-1.0µAdc, ±2% FS with multipliers x1, x10, x100, x1k, x10k |
Guard/ground load return: | Yes |
Megohmmeter: | Scaled 100 -1MΩ with multipliers of x0.1, x1, x10, x100, x1k |
Controls | |
---|---|
Voltage output: | Continuously adjustable up to max. voltage |
Safety | |
Interlocks: | Zero start and external interface |
Protection: | Surge and transient |
Cable Length | |
---|---|
Output cable: | None: Fibre glass cylinder with spinning (top toroid) output |
Ground lead: | 6m with alligator clamp |
Return lead: | 6m with alligator clamp |
Input line cord: | 3m |
Ground stick: | 6m lead and clamp included |
Size & Weight | |
Controls: | 356mm w x 279mm d x 356mm h, 15kg |
HV Tank: | 914mm base x 381mm dia cylinder x 1105mm h, 172kg |