MTE HYDROCAL 1004 genX Online Individual Dissolved Gas Analysis

The new HYDROCAL 1004 genX is the first truly maintenance-free multi-gas online DGA solution combining proven near infrared (NIR) measuring technology with vacuum protected membrane extraction.

As Hydrogen (H2) is involved in nearly every fault of the insulation system of power transformers and Carbon Monoxide (CO) is a sign of an involvement of the cellulosic / paper isolation the presence and increase of Acetylene (C2H2) further classifies the nature of a fault as overheating, partial discharge or high energy arcing.

Datasheet

MTE HYDROCAL 1004 genX Online Individual Dissolved Gas Analysis

Description

Technical information for HYDROCAL 1004 genX

General

Optional nominal voltages
of auxiliary supply:l
120 V -20% +15% AC 50/60 Hzor
230 V -20% +15% AC 50/60 Hzor
130 V +15% DC
Power consumption: max. 240 VA
Housing: Aluminium
Dimensions: W 250 x H 250 x D 286 mm
Weight: Approx. 8 kg
Operation temperature:
(ambient)
-55°C … +55°C
(below -10°C display function locked)
Oil temperature:
(inside transformer)
-20°C … +105°C
Storage temperature:
(ambient)
-20°C … +65°C
Oil Pressure: up to 800 kpa
(NO negative pressure allowed)
Connection to valve: G 1½” DIN ISO 228-1
or
1½” NPT ANSI B 1.20.1

Safety

Insulation protection: IEC 61010-1
Degree of protection: IP-55
HYDROCAL gen X Comparison
HYDROCAL 1004 genX animated HYDROCAL 1006 genX animated HYDROCAL 1011 genX animated HYDROCAL 1011 genX P animated
1004 gen X 1006 gen X 1011 gen X 1011 gen X P
(portable)
Hydrogen (H2)
Moisture in Oil (H2O)
Carbon Monoxide (CO)
Carbon Dioxide (CO2)
Methane (CH4)
Acetylene (C2H2)
Ethylene (C2H4)
Ethane (C2H6)
Oxygen (O2)
Nitrogen (N2)
Propane (C3H8)

 

If you have any further questions or would like a quotation please contact our sales team.

Additional information

Weight 15 kg
Dimensions 263 × 263 × 327.5 mm
Operation temperature (ambient)

-55°C … +55°C

Oil temperature (inside Transformer)

-20°C … +90°C

Storage temperature (ambient)

20°C … +65°C

Oil pressure

0 – 800 kpa (negative pressure allowed)

Connection to valve

G 1½" DIN ISO 228-1 or 1½” NPT ANSI B 1.20.1

Safety - Isolation protection

IEC 61010-1:2002 CE certified

Safety - Degree of protection

IP-55 CE certified

Product Enquiry