Description
“69 kV Cable Withstand & 115kV Cable Diagnostics”
Input: | 230V, 50/60Hz, 30A peak, 25A average |
Output: | 0-120kVac peak, 0.1/0.05/0.02/0.01Hz sinusoidal |
Duty: | Continuous |
Load Rating: | 0.55μF @ 0.1Hz, 1.1μF @ 0.05Hz, 2.75μF @ 0.02Hz, 5.5μF @ 0.01Hz |
Voltmeter: | 3.5″, 0 – 120kVac peak, 2% FS accuracy |
Charging Currentmeter: | 3.5″, 0 – 100mAac peak 5% FS accuracy |
Load capacitance: | 0 – 6μF |
Controls | |
Test duration timer: | User programmable |
Cable Lengths: | |
Output cable: | 30m Shielded EPR on reel |
Ground cable: | 30m on reel |
Sizes & Weight: | |
Controls: | 432mm w x 280mm d x 241mm h, 9kg |
HV Tank: | 660mm w x 508mm d x 559mm h, 177kg |
Regulator: | 508mm w x 356mm d x 686mm h, 73kg |
Overall: | 762mm w x 1524mm d x 1295mm h, 388kg |