Description
The HYDROCAL 1001+ is a permanently installed composite gas-in-oil sensor for the analysis of the following dissolved key fault gases (TDCG = Total Dissolved Combustible Gases):
Fault Gas | TDCG Contribution |
---|---|
Hydrogen (H2) | approx. 20 % |
Carbon Monoxide (CO) | approx. 30 % |
Methane (CH4) | < 5 % |
Acetylene (C2H2) | 100 % |
Ethylene (C2H4) | approx. 32 % |
Ethane (C2H6) | < 5 % |
To provide an even more comprehensive transformer monitoring solution, the HYDROCAL 1001+ analyses additionally the content of moisture (H2O) in the transformer oil.
The integration of 6 relevant key gases into a total weighted gas concentration and the measurement of Moisture in oil enables the HYDROCAL 1001+ to react to most transformer faults and makes the device to a compact and cost-effective tool used for early transformer fault detection and preventative maintenance.
Key advantages:
- Composite measurement of Hydrogen (H2), Carbon Monoxide (CO), Methane (CH4), Acetylene (C2H2), Ethylene (C2H4), Ethane (C2H6) and dissolved Moisture (H2O) in the transformer oil
- Relay outputs with light indicators showing potential alerts
- Easy and fast installation without any operational interruption of the transformer
- Compact and resistant design for long lasting usage
- Communication interfaces ETHERNET 10/100Mbit/s (copperwired or fibre-optical) and CAN bus to support proprietary communication protocols and to be prepared for sub-station communication protocols MODBUS®TCP and CANopen
HYDROCAL Comparison
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
|
1001+ | 1003 | 1005 | 1008 | 1009 | 1011 | |
Hydrogen (H2) | ○ | ● | ● | ● | ● | ● |
Moisture in Oil (H2O) | ● | ● | ● | ● | ● | ● |
Carbon Monoxide (CO) | ○ | ● | ● | ● | ● | ● |
Carbon Dioxide (CO2) | ● | ● | ● | |||
Methane (CH4) | ○ | ● | ● | ● | ||
Acetylene (C2H2) | ○ | ● | ● | ● | ● | |
Ethylene (C2H4) | ○ | ● | ● | ● | ● | |
Ethane (C2H6) | ○ | ● | ● | ● | ||
Oxygen (O2) | ● | ● | ||||
Nitrogen (N2) | ● | |||||
Propane (C3H8) | ● |