Description
“0–60 kVac and 0–100 kVac”
The DTS-60D and the DTS-100D each have the following features:
- Three motorized rates of rise: 500V/2000V/3000V per second
- Rate of rise selector switch
- Arc detection with automatic shutdown
- Zero Start safety and test chamber interlock provision
- One-piece portable design
- Window panel for test observation
- Failure indicator
- Accessory outlet located within test chamber
High Voltage, Inc. offers 60kV and 100kV test cells capable of testing to ASTM D877 and D1816 and IEC 156 standards.
The DTS-60AF is a fully automatic liquid dielectric test set, typically used for testing the voltage breakdown level of insulating oils. The most commonly used testing standards are pre-programmed into the controls. Just hit the start button and the test is performed. Custom test sequences can also be programmed. The results are stored internally for downloading to a computer and/or for printing on the printer included.
DTS-60D | DTS-100D | |
Input | 120V, 60Hz, 7 Amps or 230V, 50/60Hz, 4 Amps |
120V, 60Hz, 7 Amps or 230V, 50/60Hz, 4 Amps |
Output | 0 – 60 kVac, 800 VA Resistive Load |
0 – 100 kVac, 800 VA Resistive Load |
Output Termination | Dual capacitively graded bushings with cradle contact mounting in test chamber | Dual high voltage sections with brass corona spheres mounting in test chamber |
Testing Standards | ASTM D877,ASTM D1816, IEC 156 | ASTM D877, ASTM D1816, IEC 156 |
Gap Gauges Available | 0.04″ / 0.08″ / 0.10″ ± 0.0002″ 1 mm / 2 mm / 2.5 mm ± 0.005 mm |
0.04″ / 0.08″ / 0.10″ ± 0.0002″ 1 mm / 2 mm / 2.5 mm ± 0.005 mm |
Operating Te mperature | -14°F to 104°F -10°C to 40°C |
-14°F to 104°F -10°C to 40°C |
Distortion | <5% | <5% |
Kilovolt Meter and Accuracy | 3.5 Digit LED, Scaled 0 – 60 kVac RMS 2% of full scale |
3.5 Digit LED, Scaled 0 – 100 kVac RMS 2% of full scale |
Dimensions and Weight | 15″w x 14″d x 11.5″h, 65 lbs. 381 mm w x 356 mm d x 292 mm h, 29 kg |
18.5″w x 16.5″d x 16.5″h, 100 lbs. 470 mm w x 419 mm d x 419 mm h, 45 kg |