Quality

AS9100D

Health & Safety

ISO 45001

Environmental

ISO 14001

+44 (0) 1424 205140

Oil Dielectric Test Sets – Insulating Fluid Breakdown Voltage Testers by High Voltage INC (HVI)

The DTS Series of Oil/Liquid Dielectric AC test sets provide repeatable and accurate measurement of the breakdown voltage of insulating fluids used in transformers, circuit breakers, bushings, capacitors, etc. The test sets are rugged, reliable, and designed with field use in mind.

DTS 60-100(D)

DTS-60(A)F

This product is currently out of stock and unavailable.

Oil Dielectric Test Sets – Insulating Fluid Breakdown Voltage Testers by High Voltage INC (HVI)

Description

“0–60 kVac and 0–100 kVac”

The DTS-60D and the DTS-100D each have the following features:

  • Three motorized rates of rise: 500V/2000V/3000V per second
  • Rate of rise selector switch
  • Arc detection with automatic shutdown
  • Zero Start safety and test chamber interlock provision
  • One-piece portable design
  • Window panel for test observation
  • Failure indicator
  • Accessory outlet located within test chamber

High Voltage, Inc. offers 60kV and 100kV test cells capable of testing to ASTM D877 and D1816 and IEC 156 standards.

The DTS-60AF is a fully automatic liquid dielectric test set, typically used for testing the voltage breakdown level of insulating oils. The most commonly used testing standards are pre-programmed into the controls. Just hit the start button and the test is performed. Custom test sequences can also be programmed. The results are stored internally for downloading to a computer and/or for printing on the printer included.

DTS-60D DTS-100D
Input 120V, 60Hz, 7 Amps
or 230V, 50/60Hz, 4 Amps
120V, 60Hz, 7 Amps
or 230V, 50/60Hz, 4 Amps
Output 0 – 60 kVac, 800 VA
Resistive Load
0 – 100 kVac, 800 VA
Resistive Load
Output Termination Dual capacitively graded bushings with cradle contact mounting in test chamber Dual high voltage sections with brass corona spheres mounting in test chamber
Testing Standards ASTM D877,ASTM D1816, IEC 156 ASTM D877, ASTM D1816, IEC 156
Gap Gauges Available 0.04″ / 0.08″ / 0.10″ ± 0.0002″
1 mm / 2 mm / 2.5 mm ± 0.005 mm
0.04″ / 0.08″ / 0.10″ ± 0.0002″
1 mm / 2 mm / 2.5 mm ± 0.005 mm
Operating Te mperature -14°F to 104°F
-10°C to 40°C
-14°F to 104°F
-10°C to 40°C
Distortion <5% <5%
Kilovolt Meter and Accuracy 3.5 Digit LED, Scaled 0 – 60 kVac RMS
2% of full scale
3.5 Digit LED, Scaled 0 – 100 kVac RMS
2% of full scale
Dimensions and Weight 15″w x 14″d x 11.5″h, 65 lbs.
381 mm w x 356 mm d x 292 mm h, 29 kg
18.5″w x 16.5″d x 16.5″h, 100 lbs.
470 mm w x 419 mm d x 419 mm h, 45 kg

Additional information

Weight N/A
Dimensions N/A
Model

DTS-60D, DTS-100D, DTS-60A(F), Oil Cups

Product Enquiry

Please contact our sales for the product information. E-mail : [email protected]